Effects of Refrigerant Charge on COP
Effects of Refrigerant Charge on COP
Points : effects of refrigerant charge on cop
The COP of the capillary tube system as a function of water temperature entering the condenser
and refrigerant charge. As the water temperature entering the condenser increased, the COP was
significantly dropped at all charge amounts due to a higher power consumption and lower cooling
capacity. For the capillary tube system as the charge amount deviated from the full charge the
reduction of COP was more significant at undercharged conditions than that at overcharged
conditions. This trend was also reported by Farzard & O’Neal. The COP was reduced by 16.1% and
4.8% at 20% and +20% of full charge, respectively, at a water temperature of 3 4°C.